Welcome to BKPOWER!

Single-Phase Line-Interactive UPS (2000VA/1600W)丨BK-L11-2KVA
PRODUCT PARAMETERS
- Ultra-Clean Pure Sine Wave Output
- Ultra-Wide Input Voltage Adaptability
- High-Speed 4ms Power Transfer
- Intelligent Energy-Saving Charging
- Comprehensive Multi-Level Protection
Description
Product Overview
The BK-L11-2KVA Line-Interactive UPS (Pure Sine Wave) is a high-performance UPS uninterruptible power supply and advanced UPS System, engineered for home UPS (UPS for home), Small-office UPS, IT infrastructure, precision instruments, and professional power protection scenarios. As part of the 1000VA-3000VA capacity series, this Line-Interactive UPS integrates cutting-edge automatic voltage regulation (AVR) technology, a wide input voltage range, and flexible battery expansion, tailored for compact installation in home, small office, and professional environments. It delivers stable, high-quality UPS power for key electronic devices, precision equipment, and daily-use appliances—becoming the preferred choice for users seeking reliable power backup, voltage stabilization, and efficient energy use.
Applications
This Line-Interactive UPS (UPS Uninterruptible Power Supply) is a versatile UPS System, widely applied in home, small office, and professional scenarios to provide targeted, reliable UPS power protection:
UPS for Home & Residential Use
Perfect for home entertainment systems (high-definition audio/television), desktop computers, external storage devices, and home security monitoring systems. As a dedicated home UPS, it ensures uninterrupted daily use, preventing data loss and equipment damage caused by power outages or voltage fluctuations.
Small-office UPS & SOHO Applications
Ideal for small office IT infrastructure such as workstations, network equipment (routers/switches), storage devices, printers, and scanners. This Small-office UPS maintains seamless office operations by stabilizing unstable mains power, providing emergency backup, and safeguarding critical business data.
Professional & Precision Equipment
Suitable for medical devices (monitors, diagnostic equipment), laboratory analytical instruments, audio-visual production gear, and industrial control devices. The pure sine wave UPS power ensures accurate, stable operation of sensitive equipment, meeting professional performance requirements.
Product Features
As a high-performance Line-Interactive UPS and UPS Uninterruptible Power Supply, this UPS System combines the advantages of home UPS, Small-office UPS, and professional UPS power solutions with the following core features:
Wide Input Voltage Range
Adapts to harsh mains voltage fluctuations, reducing battery switching frequency to extend service life—ideal for unstable power environments in home, small office, and professional settings.
Pure Sine Wave UPS Power Output
Delivers high-quality pure sine wave output with THD <3% (linear load) and <6% (non-linear load), fully matching the power requirements of high-precision devices and sensitive electronics in home, small office, and professional applications.
Advanced AVR for Stable UPS Power
Automatic Voltage Regulation (AVR) technology dynamically adjusts input voltage deviations, balancing efficiency and protection to ensure consistent 220VAC output— a key advantage for home UPS and Small-office UPS users needing reliable voltage stabilization.
Intelligent Charging & Extended UPS Power Backup
Supports fast charging (recovers to 90% capacity in 4 hours for built-in batteries) and adjustable charging current (1A/2A/4A/6A for external batteries), maximizing battery life and flexible backup time for both UPS for home and Small-office UPS needs.
4ms Fast Transfer Time
Instantly switches between mains and battery modes under standard conditions, avoiding data corruption and equipment failure—critical for protecting valuable data and sensitive devices in all application scenarios.
Specifications
| Model item | BK-L11-2KVA | |
| Capacity | 2000VA/1600W | |
| Topology | Online interactive | |
| Efficiency | AC Mode | ≥88% |
| Battery Mode | ≥85% | |
| Input | Rated Voltage | 220VAC |
| Voltage Range | 145Vac-275Vac | |
| Frequency | 50/60Hz±3Hz (Auto sensing) | |
| Phase | Single-phase | |
| Power Factor | ≥0.99@220-230VAC | |
| Output | Rated Voltage | 220VAC |
| Frequency Range (Synchronous Range) | Follows mains when input is 47-53Hz (50Hz default) or 57-63Hz (60Hz default) | |
| Frequency Range (Battery Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
| Transfer Time | 4ms (standard conditions) | |
| Waveform (Battery Mode) | Pure Sine Wave | |
| THD | <3% (linear load), <6% (non-linear load) | |
| Current Crest Ratio | 3:1 | |
| Overload Protection | 100%-110%: audible alarm; 110%-130%: auto-shutdown after 30s or switch to bypass mode (normal input); >130%: immediate shutdown or switch to bypass mode (normal input) | |
| Battery | Built-in Battery Model | 12V/7-9AH |
| Number of Batteries | 4/6 | |
| Charging Time | 4 hours recover to 90% (built-in battery) | |
| Charging Current | Maximum 1A (built-in battery); 1A/2A/4A/6A adjustable (external battery) | |
| Charging Voltage | 54V±1%/82V±1% | |
| Environmental | Operating Temperature | 0~40℃ |
| Humidity | 20-95%RH (non-condensing) | |
| Noise | <45dBA@1m | |
| Management | Communication Interface | Optional intelligent RS-232 or USB, supporting Windows 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC |
| Optional SNMP | Supports power management via SNMP manager and web browser | |
| Dimension (D×W×H) | 315×190×320 mm | |
| Net Weight | 12.5kg / 19.15 kg | |
FAQs
UPS stands for Uninterruptible Power Supply and is a device that provides a continuous supply of power to protect critical loads from power failures or fluctuations.
The main role of a UPS is to provide a backup power source to ensure that critical equipment can continue to operate when utility power is interrupted or unstable, avoiding data loss or equipment damage.
UPS is mainly divided into three types: offline, online and online interactive.
When choosing the power capacity of the UPS, you need to consider the total power demand of the load, it is usually recommended to choose a slightly larger than the total load power of the UPS to ensure sufficient standby time.
The standby time of a UPS depends on the battery capacity and load power. Standby time usually ranges from 10 minutes to several hours, and the specific needs can be determined according to the actual application scenario.