Willkommen bei BKPOWER!

BK-L11-3KL(PF0.8)丨Single Phase High-Frequency Online UPS
PRODUKTPARAMETER
- True Online Double-Conversion Technology
- Advanced High-Frequency Transformerless Design
- Ultra-Wide Input Voltage & Frequency Range
- Hohe Effizienz und Energieeinsparung
- Full Digital DSP Control
Beschreibung
Produktübersicht
The BK-L11-3KL is a high-performance Double Conversion UPS designed for medium-to-large sensitive loads, featuring a three-phase input and single-phase output configuration. As a premium High-frequency double-conversion UPS, it adopts true online double-conversion architecture, delivering 0ms seamless transfer between mains and battery modes—completely isolating critical loads from grid fluctuations, harmonics, surges, and outages.
This Online-UPS supports customizable external battery configurations (voltage/count) to meet extended backup time needs for global users, paired with a wide input voltage range and high input power factor (≥0.99 at full load). As a Transformerless online UPS (high-frequency design), it outputs a stable pure sine wave with low harmonic distortion, making it an ideal Unterbrechungsfreie Stromversorgung for industrial control systems, data centers, medical equipment, and other mission-critical scenarios across North America, Europe, and Southeast Asia.
With 91% efficiency and compact dimensions, this USV-Anlage balances performance and space-saving—perfect for overseas facilities with limited installation space. It serves as a reliable Backup Power Supply for businesses seeking cost-effective, high-reliability power protection without compromising on global power quality standards.
Anwendungen
This versatile online UPS caters to diverse high-reliability scenarios for overseas users, leveraging its three-phase input and external battery flexibility:
Industrial Control Systems
Protects PLCs, automated production lines, CNC machines, and industrial robots. This Double Conversion UPS withstands grid instability and suppresses electromagnetic interference, avoiding costly production downtime for global manufacturing plants.
Data Centers & IT Rooms
Powers servers, storage arrays, and network switches. The 0ms transfer time of this High-frequency double-conversion UPS prevents data loss, while low harmonic distortion ensures compatibility with precision IT equipment in overseas data centers.
Medizinische Ausrüstung
Supports high-power medical devices (e.g., diagnostic scanners, laboratory instruments). This Uninterruptible Power Supply delivers stable output voltage and low leakage current, meeting medical-grade power quality requirements for global healthcare facilities.
Commercial Infrastructure
Covers financial server rooms, communication base stations, and smart building control systems. The wide input range of this UPS System adapts to complex urban grid environments in overseas commercial hubs.
Energy & Transportation
Powers new energy station monitoring systems, substation automation equipment, and rail transit signal systems. With >91% efficiency, this Backup Power Supply reduces long-term energy costs for international energy and transportation projects.
Produktmerkmale
Three-Phase Input/Single-Phase Output Design
Adapted to medium-to-large three-phase power systems worldwide, while supporting single-phase sensitive loads—ideal for overseas industrial and commercial scenarios where three-phase grid access is available but loads require single-phase power.
True Double Conversion UPS Architecture
0ms transfer time between mains and battery modes; the inverter powers the load continuously, eliminating downtime risks for critical equipment. This core feature of Double Conversion UPS ensures seamless protection against all grid anomalies.
High-Frequency Online UPS Design
Leverages a transformer-less high-frequency topology, enhancing power density and reducing energy loss—aligning with global energy-saving trends and lowering operational costs for overseas users.
Wide Input Voltage Adaptability
Handles grid sags and surges without frequent battery activation, adapting to unstable grid conditions in emerging and developed markets alike.
Low Harmonic Distortion Output
Pure sine wave output with THD <3% (linear load), avoiding interference with precision electronics—critical for medical devices, IT gear, and industrial control systems that demand high power quality.
Customizable External Battery Management
Supports customizable battery voltage and count, with multi-stage charging technology. This flexibility allows overseas users to tailor backup time to their specific needs, extending battery cycle life and reducing replacement costs.
Comprehensive Overload Protection
Multi-stage overload handling in AC and battery modes safeguards the USV-Anlage and connected devices from damage, complying with international safety standards for commercial and industrial use.
Spezifikationen
| Modell | BK-L11-3KL(PF0.8) | |
| Kapazität | 3000VA/2400W | |
| Phase | Single Phase with Ground | |
| AC-Eingang | Nennspannung | 208VAC/220VAC/230VAC/240VAC |
| Spannungsbereich | 110-160VAC (50% load); 160-280VAC (100% load) | |
| Frequenzbereich | 40Hz-70Hz | |
| Leistungsfaktor | ≥0.99 (100% load) | |
| THDi | ≤5%@ nominal voltage(100% load) | |
| Batterie-Eingang | Akku-Spannung | 72V |
| Battery Connection | Internal Battery | |
| Ladespannung | 82.1VDC±1% | |
| Ladestrom | 1A | |
| Recharge Time | 5hours to 90% | |
| AC-Ausgang | Nennspannung | 208VAC/220VAC/230VAC/240VAC |
| Spannungsregelung | ±1% | |
| Frequenz | 50Hz±0.25Hz; 60Hz±0.25Hz | |
| THD | ≤3% (linear load); ≤6% (non-linear load) | |
| Leistungsfaktor | 0.8 | |
| Overload Capability | AC Mode :100%-110%: 10min; 110%-130%: 1min; >130%: 1sec | |
| Current Crest Ratio | Battery Mode: 100%-110%: 30sec; 110%-130%: 10sec; >130%: 1sec | |
| 3:1 | ||
| Übertragungszeit | 0ms | |
| Wirkungsgrad | AC-Modus | 90% |
| Akku-Modus | 88% | |
| Indicators | LCD | Load Level,Battery Level,AC Mode,Battery Mode,Bypass Mode,and Fault Indicator Via LCD |
| Umwelt | Luftfeuchtigkeit | <95% RH (non-condensing) |
| Betriebstemperatur | 0~40℃ | |
| Lärmpegel | ≤50dB@1meter | |
| Communication & Monitoring | RS232 (485 optional); Smart slot (SNMP optional); SMS alert (optional) | |
| Gewicht | 24.5KG | |
| Dimensions (D×W×H) | 430×190×323 mm | |
Kindly note: The technical parameters provided here are for reference only and are intended as a selection guide. Given that the product offers various customization options, such as powAer rating, voltage configuration, battery solutions, and special certifications, the final product specifications will be subject to the final order document.
FAQs
UPS steht für Uninterruptible Power Supply (unterbrechungsfreie Stromversorgung) und ist ein Gerät, das eine kontinuierliche Stromversorgung bietet, um kritische Verbraucher vor Stromausfällen oder -schwankungen zu schützen.
Die Hauptaufgabe einer USV besteht darin, eine Ersatzstromquelle bereitzustellen, um sicherzustellen, dass kritische Geräte auch bei einer Unterbrechung oder Instabilität der Stromversorgung weiter betrieben werden können, um Datenverlust oder Geräteschäden zu vermeiden.
Der USV wird hauptsächlich in drei Arten unterteilt: offline, online und online interaktiv.
Bei der Wahl der Leistungskapazität der USV müssen Sie den Gesamtstrombedarf der Last berücksichtigen. Es wird in der Regel empfohlen, eine etwas größere Leistung als die Gesamtlast der USV zu wählen, um eine ausreichende Standby-Zeit zu gewährleisten.
Die Standby-Zeit einer USV hängt von der Batteriekapazität und der Lastleistung ab. Die Standby-Zeit reicht in der Regel von 10 Minuten bis zu mehreren Stunden, wobei die spezifischen Anforderungen je nach Anwendungsszenario festgelegt werden können.
.png)
.png)














-768x768.jpg)
-main-768x768.jpg)